Can I place the V1K anywhere on the output side of the drive?

The V1K output filter is designed to be located directly next to the VFD. TCI recommends the filter be located within 10 feet of the drive to properly handle the voltage distortion, dV/dt, before it escalates on the line and causes damage to the motor and lead cables. If this is not possible due to the location or configuration of the drive system, we recommend our customers contact TCI Technical Support to discuss the application and ways to address this situation.