FAQ - Are communication and control features available with the H5?

Yes, there is an RS232 com port and relay contacts for remote start/stop and fault alarm indication.

FAQ - Can H5 factory settings be changed to fix displacement power factor before reducing harmonics?

The H5’s programming can be changed to accommodate the adjustment in primary functions; however, this would become a custom filter.

FAQ - Can the H5 be applied on systems containing DC drives?

The H5 is not currently configured to operate on DC converter loads.

FAQ - Is startup factory commissioning required for the H5?

Factory commissioning is not required. The H5 should be fully operational immediately upon installation per the guidelines within the Installation, Operation, & Maintenance manual.

FAQ - Will the H5 correct displacement power factor?

The H5 will keep the current in phase with the line voltage, however, if it reaches full capacity, the distortion power factor will increase and the total power factor (KW/KVA) will decrease from unity. If additions to the system cause the H5 to reach full capacity, additional H5 units can be installed to correct the situation.